Why this log matters
Under the Regulatory Reform (Fire Safety) Order 2005, the responsible person must keep fire safety equipment in efficient working order and good repair (Article 17). The Home Office guidance says it is good practice to record all tests, false alarms and maintenance, and that a log book helps you show the fire service you have complied. This page follows the guidance for England; Scotland and Northern Ireland have their own fire safety law, with similar duties.
What the guidance recommends
| Check | How often | Who |
|---|---|---|
| Activate a manual call point, using a different one each time | Weekly | You or a trained member of staff |
| Check the control and indicating panel | At least every 24 hours | You or a trained member of staff |
| Servicing and preventive maintenance | Every six months | A competent person |
Further detail on testing and maintenance is in British Standard BS 5839-1, which your alarm engineer will work to. Test at the same time each week so staff know it is a test, and rotate through every call point so each one is proven over time.
What to do if a test fails
- Write down exactly what happened: no sound, not heard in one area, or a fault on the panel.
- Call your alarm engineer the same day.
- Until it is fixed, put interim measures in place, such as briefing staff and checking the affected area more often. Your fire risk assessment should say what these are.
- Retest once repaired and record the result.
With the digital version, a missed weekly test triggers a reminder and can be escalated to a manager, and photos of engineer reports sit next to the test entries.